YOU MIGHT ALSO LIKE
ASSOCIATED TAGS
breaker  breakers  circuit  contactor  contacts  coordination  damage  guarantee  industrial  people  prevent  protection  safety  standard  systems  
LATEST POSTS

What Is Type 2 Protection? The Real Story Behind the Safety Standard You’ve Probably Misunderstood

What Is Type 2 Protection? The Real Story Behind the Safety Standard You’ve Probably Misunderstood

We’re talking about an engineering specification buried in IEC 60947, yet one that quietly shapes how factories keep running. And if you're involved in industrial automation, power distribution, or plant safety, this isn't just theory. This is the difference between a 30-minute repair and a 3-day outage.

Understanding Type 2 Protection: Not Just a Label, But a Promise

You see "Type 2 coordination" stamped on a component datasheet and assume everything’s covered. That’s where it gets dangerous. The thing is, Type 2 protection isn’t a guarantee of perfection—it’s a guarantee of control. It says that when a short circuit hits, the motor starter assembly will protect people and prevent catastrophic failure, even if some parts need replacing afterward.

Short-circuit protection devices (SCPDs), like fuses or molded case circuit breakers (MCCBs), work in tandem with contactors and thermal overloads. The coordination level—Type 1, 2, or sometimes 3—defines how they behave together under fault conditions. Type 2 allows for contactor damage, as long as no fire, molten metal, or hazardous voltage exposure occurs. And that’s acceptable. Because keeping people alive beats saving a $400 contactor.

But here’s where reality bites: not all manufacturers test this the same way. Some simulate faults with ideal conditions. Others use real-world stress—repeated tripping, dirty terminals, aged components. And that changes everything.

The Difference Between Type 1, Type 2, and Type 3 Coordination

Type 1 coordination is the bare minimum. After a short circuit, the system must remain safe—but the contactor can be welded shut or destroyed beyond recognition. You’re allowed to replace the entire starter. Fine for non-critical systems. Not fine when uptime matters.

Type 2 is the industry sweet spot. After a fault, the contactor may be damaged—contacts pitted, auxiliary circuits compromised—but it must still be safely isolatable. No risk of spontaneous restart. No exposed live parts. Maintenance crews can lock it out, swap the damaged components, and be back online fast. Siemens, ABB, and Eaton all design for Type 2 as standard in most industrial motor applications—especially those above 5.5 kW.

Type 3? That’s the gold standard. No damage at all. The starter survives repeated short circuits unscathed. But it’s expensive. We’re talking about $1,800 starters where a Type 2 equivalent costs $650. And honestly, for most applications, it’s overkill. Only critical processes—like hospital HVAC or chemical processing lines—justify that cost.

Why Type 2 Coordination Matters in Real-World Installations

Let’s say you’re managing a bottling plant in Lisbon. Three shifts. 92 motors driving conveyors, fillers, cappers. A fault hits on a 15 kW pump motor. If you’ve got Type 1 coordination, the contactor welds shut. The motor keeps running. Overheats. Fire risk. Production halts. Total downtime: 14 hours. Repair cost: €4,200.

Same scenario with Type 2? The breaker trips. The contactor’s contacts are scorched—maybe even fused slightly—but the mechanical linkage holds. The system is de-energized. Safe to service. Replacement takes 45 minutes. Downtime: under an hour. Cost: €320 for a new contactor block. That’s not just better engineering. That’s better business.

How Does Type 2 Protection Work? Inside the Physics and Design

Motors draw massive current when starting—up to 6-7 times their rated load. That’s normal. A short circuit? That can spike to 50,000 amps in milliseconds. The protection system has less than 20 milliseconds to react before thermal and magnetic forces rip components apart.

Rapid arc quenching is the hero here. In Type 2 systems, the fuse or circuit breaker must clear the fault before the contactor’s internal arc becomes uncontrollable. Fuses are faster—some blow in 8 milliseconds at high fault currents. Circuit breakers rely on magnetic trip units, which can take 12–18 ms. Either way, the timing is brutal, and coordination is everything.

And here’s the catch: coordination isn’t just about speed. It’s about energy let-through—the I²t value (thermal stress integral). Even if the breaker trips fast, if it lets through too much energy, it fries the contactor’s coil or welds the contacts. Type 2 coordination demands that the SCPD limits I²t to a level the contactor can survive—at least structurally.

But because testing is destructive, manufacturers simulate these events using software like ETAP or SKM, then validate with lab tests at accredited facilities—UL in the U.S., TÜV in Germany, IMQ in Italy. Still, field conditions vary. Voltage sags, harmonic distortion, dust buildup—they all affect performance. Data is still lacking on long-term degradation under repeated minor faults.

The Role of Fuses vs. Circuit Breakers in Type 2 Systems

Fuses have a dirty reputation—they’re “old school,” people say. But in Type 2 protection, they’re often superior. A high-performance fuse like the Ferraz Shawmut A6Q series can clear a 100 kA fault in under 10 ms. That’s faster than most breakers. And they’re cheaper—$90 versus $280 for an equivalent MCCB.

But—and this is a big but—you can’t reset a fuse. Every fault means replacement. In a remote pumping station in Alberta, that could mean a 2-hour truck drive just to swap a $12 component. Circuit breakers win on convenience, even if they’re slightly slower and cost more.

So which do you choose? If uptime is everything, go breaker. If cost and speed matter more, fuse it. There’s no universal answer. Experts disagree, and rightly so.

Coordination Charts: Your Best Friend or Worst Trap?

Manufacturers provide coordination tables—dense grids matching contactors to fuses or breakers, rated for Type 2 performance up to a certain fault current (say, 100 kA). These are gospel—until they’re not.

I once saw a plant in Ohio use a coordination chart that hadn’t been updated since 2016. They installed a new 75 kW motor, pulled the “approved” fuse rating from the table, and two weeks later, a fault turned the contactor into a smoking paperweight. Why? The chart was for an older contactor model with different arc chutes. The I²t tolerance had dropped by 34%. No one noticed.

Which explains why you must check the revision date, cross-reference with the exact product codes, and verify the test standard: IEC 60947-4-1, Annex F. Because one digit off in a part number can void the entire Type 2 rating.

Type 2 vs. Selective Coordination: When Protection Gets Smarter

Type 2 is about local safety. Selective coordination is about system-wide intelligence. The goal? Only the breaker closest to the fault trips—no unnecessary cascading shutdowns.

Imagine a distribution board feeding 12 machines. A short circuit on Motor 7. With non-selective protection, the main breaker trips. Everything stops. With selective coordination, only the branch breaker for Motor 7 opens. Production continues elsewhere.

But achieving selectivity isn’t free. It requires time-delayed breakers, zone interlocking, or advanced relays. And it doesn’t always play nice with Type 2. Why? Because delaying a breaker to allow selectivity increases let-through energy—which can push a contactor past its Type 2 survival threshold.

The issue remains: you can’t always have both. Either you get selectivity or you guarantee Type 2. Sometimes, you compromise—accepting limited damage in exchange for isolation. It’s a trade-off engineers hate making, but make they must.

Frequently Asked Questions About Type 2 Protection

Does Type 2 Protection Mean No Equipment Damage?

No. That’s a common myth. Type 2 allows for damage—contactor contacts may be welded, the coil burned, auxiliary circuits disrupted. But the assembly must remain enclosed, safe to touch, and prevent re-energization without manual intervention. You might need to rebuild the contactor, but you won’t need a fire extinguisher.

How Do I Verify Type 2 Coordination in My System?

Start with the manufacturer’s coordination tables. Confirm the exact models of your contactor, overload relay, and SCPD. Check the fault current at the motor terminal—don’t assume it’s the same as at the main panel. Use software like EasyPower to simulate fault levels. And if you’re in a high-risk environment—offshore, mining, petrochemical—demand test reports from the supplier. Don’t take a datasheet at face value.

Is Type 2 Required by Safety Codes?

Not explicitly. But IEC 60204-1 (safety of machinery) requires that control systems prevent hazardous situations during faults. Type 2 coordination is the most cost-effective way to meet that. In North America, NFPA 79 implies similar expectations. So while no code says “thou shalt use Type 2,” it’s the de facto standard for anything beyond basic machinery.

The Bottom Line: Type 2 Isn’t Perfect—But It’s What We’ve Got

I am convinced that Type 2 protection strikes the right balance for most industrial applications. It’s not flawless. It doesn’t prevent downtime. It won’t save every component. But it keeps people safe and limits chaos when things go wrong—which they will.

My advice? Don’t treat Type 2 as a checkbox. Treat it as a living specification. Audit your coordination tables annually. Re-validate after any system upgrade. And never, ever assume a label means immunity. Because in the real world, safety isn’t about perfection. It’s about control.

And that’s exactly where Type 2 delivers. We’re far from it being a magic bullet—but for now, it’s the best shield we’ve got between a short circuit and a shutdown that costs six figures. Suffice to say, ignoring it isn’t an option.

💡 Key Takeaways

  • Is 6 a good height? - The average height of a human male is 5'10". So 6 foot is only slightly more than average by 2 inches. So 6 foot is above average, not tall.
  • Is 172 cm good for a man? - Yes it is. Average height of male in India is 166.3 cm (i.e. 5 ft 5.5 inches) while for female it is 152.6 cm (i.e. 5 ft) approximately.
  • How much height should a boy have to look attractive? - Well, fellas, worry no more, because a new study has revealed 5ft 8in is the ideal height for a man.
  • Is 165 cm normal for a 15 year old? - The predicted height for a female, based on your parents heights, is 155 to 165cm. Most 15 year old girls are nearly done growing. I was too.
  • Is 160 cm too tall for a 12 year old? - How Tall Should a 12 Year Old Be? We can only speak to national average heights here in North America, whereby, a 12 year old girl would be between 13

❓ Frequently Asked Questions

1. Is 6 a good height?

The average height of a human male is 5'10". So 6 foot is only slightly more than average by 2 inches. So 6 foot is above average, not tall.

2. Is 172 cm good for a man?

Yes it is. Average height of male in India is 166.3 cm (i.e. 5 ft 5.5 inches) while for female it is 152.6 cm (i.e. 5 ft) approximately. So, as far as your question is concerned, aforesaid height is above average in both cases.

3. How much height should a boy have to look attractive?

Well, fellas, worry no more, because a new study has revealed 5ft 8in is the ideal height for a man. Dating app Badoo has revealed the most right-swiped heights based on their users aged 18 to 30.

4. Is 165 cm normal for a 15 year old?

The predicted height for a female, based on your parents heights, is 155 to 165cm. Most 15 year old girls are nearly done growing. I was too. It's a very normal height for a girl.

5. Is 160 cm too tall for a 12 year old?

How Tall Should a 12 Year Old Be? We can only speak to national average heights here in North America, whereby, a 12 year old girl would be between 137 cm to 162 cm tall (4-1/2 to 5-1/3 feet). A 12 year old boy should be between 137 cm to 160 cm tall (4-1/2 to 5-1/4 feet).

6. How tall is a average 15 year old?

Average Height to Weight for Teenage Boys - 13 to 20 Years
Male Teens: 13 - 20 Years)
14 Years112.0 lb. (50.8 kg)64.5" (163.8 cm)
15 Years123.5 lb. (56.02 kg)67.0" (170.1 cm)
16 Years134.0 lb. (60.78 kg)68.3" (173.4 cm)
17 Years142.0 lb. (64.41 kg)69.0" (175.2 cm)

7. How to get taller at 18?

Staying physically active is even more essential from childhood to grow and improve overall health. But taking it up even in adulthood can help you add a few inches to your height. Strength-building exercises, yoga, jumping rope, and biking all can help to increase your flexibility and grow a few inches taller.

8. Is 5.7 a good height for a 15 year old boy?

Generally speaking, the average height for 15 year olds girls is 62.9 inches (or 159.7 cm). On the other hand, teen boys at the age of 15 have a much higher average height, which is 67.0 inches (or 170.1 cm).

9. Can you grow between 16 and 18?

Most girls stop growing taller by age 14 or 15. However, after their early teenage growth spurt, boys continue gaining height at a gradual pace until around 18. Note that some kids will stop growing earlier and others may keep growing a year or two more.

10. Can you grow 1 cm after 17?

Even with a healthy diet, most people's height won't increase after age 18 to 20. The graph below shows the rate of growth from birth to age 20. As you can see, the growth lines fall to zero between ages 18 and 20 ( 7 , 8 ). The reason why your height stops increasing is your bones, specifically your growth plates.